For the reliability analysis of the flow control loop in
Chapter 10, Problem 10.6(choose chapter or problem)
For the reliability analysis of the flow control loop in Example 10.3, the DIP flowmeter is the least reliable component. Suppose that a second, identical flowmeter is used in a backup mode so that it could be automatically and immediately employed if the first flowmeter failed. How much would the overall system reliability improve by adding the second sensor?
Questions & Answers
QUESTION:
For the reliability analysis of the flow control loop in Example 10.3, the DIP flowmeter is the least reliable component. Suppose that a second, identical flowmeter is used in a backup mode so that it could be automatically and immediately employed if the first flowmeter failed. How much would the overall system reliability improve by adding the second sensor?
ANSWER:Step 1 of 4
The given data in example 10.3 is,
Component |
Reliability |
D/P flowmeter |
0.18 |
Digital controller |
0.95 |
I/P transducer |
0.61 |
Control valve |
0.55 |
Valve positioner |
0.64 |
The reliability of D/P flowmeter is 0.18.