Figure 3.32 shows the one-line diagram of a three-phase

Chapter , Problem 3.23

(choose chapter or problem)

Figure 3.32 shows the one-line diagram of a three-phase power system. By selecting a common base of 100 MVA and 22 kV on the generator side, draw an impedance diagram showing all impedances including the load impedance in per-unit. The data are given as follows: G: 90 MVA 22 kV x = 0:18 per unit T1: 50 MVA 22/220 kV x = 0:10 per unit T2: 40 MVA 220/11 kV x = 0:06 per unit T3: 40 MVA 22/110 kV x = 0:064 per unit T4: 40 MVA 110/11 kV x = 0:08 per unit M: 66.5 MVA 10.45 kV x = 0:185 per unit Lines 1 and 2 have series reactances of 48.4 and 65.43 W, respectively. At bus 4, the three-phase load absorbs 57 MVA at 10.45 kV and 0.6 power factor lagging.

Unfortunately, we don't have that question answered yet. But you can get it answered in just 5 hours by Logging in or Becoming a subscriber.

Becoming a subscriber
Or look for another answer

×

Login

Login or Sign up for access to all of our study tools and educational content!

Forgot password?
Register Now

×

Register

Sign up for access to all content on our site!

Or login if you already have an account

×

Reset password

If you have an active account we’ll send you an e-mail for password recovery

Or login if you have your password back