Superheated refrigerant R-134a at 20°C and 0.5 MPa is
Chapter 3, Problem 114HP(choose chapter or problem)
Problem 114HP
Superheated refrigerant R-134a at 20°C and 0.5 MPa is cooled in a piston/cylinder arrangement at constant temperature to a final two-phase state with quality of 50%. The refrigerant mass is 5 kg, and during this process 500 kJ of heat is removed. Find the initial and final volumes and the necessary work.
Questions & Answers
QUESTION:
Problem 114HP
Superheated refrigerant R-134a at 20°C and 0.5 MPa is cooled in a piston/cylinder arrangement at constant temperature to a final two-phase state with quality of 50%. The refrigerant mass is 5 kg, and during this process 500 kJ of heat is removed. Find the initial and final volumes and the necessary work.
ANSWER:
Solution
Step 1 of 4
In this problem, we have to find the initial and final volumes and the necessary work.